7177H-88-ULP IntelliNet 2.0 Hybrid Subscriber

8 zone supervised fire alarm communicator with IP Link functionality. The 7177H-88-ULP Hybrid 2.0 Fire Subscriber includes 8 Zones, IntelliPro full data module and IP Link capabilities. Provides the capability to send an alarm from the customers premises to the Central Monitoring Station (CMS) via RF and/or IP. Can transmit peer signals via IP as well. UL & Canadian ULC listed and NFPA Code Compliant.

Dimensions 13”H x 8.5”W x 4.5”D

Weight 7 lbs., excludes battery

Radio Frequency Standard Frequency Range: 450-470 MHz Contact AES for other UHF and VHF frequencies

Antenna 2.5 dB tamper resistant antenna included, mounts on enclosure, and optional remote mounting antenna available

Power Output 2 Watts, Factory set Contact AES for other options

Power Input 16.5VAC and battery 24VDC and battery* 24VDC only* *(requires FACPA for isolation)

Recharge Capability 12 Ah, UL recognized lead acid gel cell, size based on subscriber configuration

Backup Battery Will charge 12V battery size 12 Ah. F2 connectors

Alarm Singnal Inputs 8 isolated dry contact zones; 1 zone is
reserved for Tamper Switch
· 7794A AES-IntelliPro full data
module included for Contact ID,
and Pulse

Antenna Cut/Communication Trouble Output Form C relay, fail secure, rated 24V DC 1A resistive, unsupervised

Antenna 2.5 dB tamper resistant enclosure mount antenna

Antenna Supervision Antenna is connected to dedicated Antenna Supervision Module (ASM) for constant antenna supervision

Reset Button Located on main circuit board

Operating Temperature 32° to 122°F

Storage Temperature 14° to 140°F

Relative Humidity 0 to 93%, non-condensing

Ports 2 USB and 1 Ethernet ports

Annunciator Integrated Local Annunciator (Remote Annunciator accessory available)

Compatible Receivers 7705i and 7705ii AES-MultiNet Receiver

Current Consumption Standby w/ charged backup battery: 200 mA (1.4 A Transmitting) Standby + charging backup battery: 900 mA (1.4 A Transmitting - MAX)

Smoke Detector Compatibility N/A

NAC Output N/A

NAC Patterns N/A

Enclosure Material Steel

Enclosure Color Red

Visual Indicators Front panel LCD with Power and Trouble LEDs. Additional LED indicators inside enclosure (ALM, Trouble, Tx, Rx, WA)

Programming Interface Laptop, smart phone, or tablet via Ethernet or integrated WiFi dongle

  • Meets NFPA 72 specifications and UL 864 standards
  • 8 zone inputs
  • Hardware Supervisory Module (satisfies full data primary communication requirements)
  • Includes AES IntelliPro Full Data Module
  • Dual Communication/Multiple communication technology (reporting over RF and IP)
  • Integrated Local Annunciator
  • Secure Dealer Codes to safeguard critical data
  • Front panel Power and Trouble LEDs and Menu/Silence button
  • Improved functionality with an adaptive graphical user interface (GUI) for programming via smartphones, tablet and PCs
  • 2.5 dB rubber duck antenna
  • Offers flexible power and configuration options
  • Provides dual functionality – subscriber and IP Link
  • Integrated Tamper Switch connected to one of the available dry contact zones
  • Wifi internet connectivity
  • Antenna supervision module (ASM)
  • Ground fault isolation transformer

Related Videos

2.0 Fire Subscriber Programming

Subscriber Location

Available Downloads

Software Update

Updating AES 2.0 with a Thumb Drive
Watch Video

Updating AES 2.0 with a Laptop and Ethernet Connection
Watch Video


Hybrid 7177H
v8.2.08

Release Date: March 2023

If currently running software v8.2.02 or older please contact tech support for correct files.

Download v8.2.08

Knowledge Base

Your source for technical solutions and case management tracking.

Skype Call

Walk through your issue over video with one of our experts.

FAQs

Get the answers to some of our most common questions.